Performance Data
CV: 2.3
Max. Flow: 20 GPM*
Min. Flow: 1 GPM
Hot Supply Temp.: 120-180˚F (49-82˚C)
Cold Supply Temp.: 39-80°F (5-27°C)
Max. Inlet Pressure: 230 PSI
Max. Variation in Supply Pressure: 20%
Min. Temp. Differential Between Hot Supply and Mixed: 10°F (5.6˚C)
Outlet Temp. Range: 85-175 F (29-80˚C)
Factory set to: 115-120˚F (41-45˚C)
Accuracy of Outlet Temp.: ± 3˚F
Connection Sizes: Sweat, NPT, Pex, CPVC Union
*NOTE: Flow should never exceed standards for pipe size.
Features
- Delivers Stable Mixed Water Temperature
- Tamper-Resistance Cap
- Low Headloss
- Outlet Temperature Strip
- Optional Dial Gauge and Adaptor
- Check Valves Included
Applications
- Radiant Heating Systems